ABB AC900F學習筆記50:Freelance_Mounting_and_Installation_AC_900F_Controller-10
3.2 CI/CM PROFIBUS modules
CI/CM PROFIBUS模板
The AC 900F is designed for operation with different PROFIBUS communicationinterfaces like the CI 930F, CI 773F and CM 772F that can be connected on the leftside of the PM CPU module。
AC 900F 專為具有不同 PROFIBUS 通訊的操作而設計,像CI 930F、CI 773F和CM 772F這樣可以在左側連線PM CPU模組的一側。
The module type CM 772F is supported by PM 901F and PM 902F, but not byPM 904F. CM 772只能被PM 901F和PM 902F,不能被PM 904F支援 |
PROFIBUS communication interfaces ensure communication via the PROFIBUSDPFieldbus. The internal coupler bus connects the CI/CM with the CPU module.This applies to data and power supply. A dual-port RAM is used for data exchange
PROFIBUS通訊介面確保通過PROFIBUS DP現場匯流排進行通訊。內部耦合器匯流排將CI/CM和CPU模板連線起來。這適用於資料和電源(指的是通過內部耦合器)。雙埠RAM適用於資料交換。
3.2.1 CI 930F PROFIBUS-DP Master Interface
CI 930F PROFIBUS-DP主站介面
The below description applies to CI 930F with ordering numbers 3BDH....R0002and ....R0005 only. CI 930F provides two on-board PROFIBUS interfaces A/B forincreased availability regarding PROFIBUS communication
以下描述僅適用於訂貨編號為3BDH....R0002和3BDH....R0005 的CI 930F,CI 930F提供了兩個板載PROFIBUS介面A/B以提升PROFIBUS通訊可用性。
LEDs for status display LED狀態顯示燈
Label 標籤
PROFIBUS Interface A Profibus通訊介面A
PROFIBUS Interface B Profibus通訊介面B
Data arriving at CI 930F via the coupler bus are routed in parallel to both A and Bconnections. The first data coming in over line A or line B with a correct telegramstart are routed to the coupler bus. With simultaneity, either line A or line B isselected at random. Testing and selection is always based on the first character. Inthe case of a telegram start with error on A, the control logic in CI 930F switches tothe redundant line B. The same procedure applies vice-versa for line B.
資料通過耦合器匯流排到達 CI 930F , A 和 B 連線為平行路由。線路A或者線路B是第一批使用正確報文開頭的資料到耦合器匯流排的路徑。伴隨同步性,選擇線路A還是線路B是隨機的。測試和選擇始終基於第一個字元、在報文開頭出錯的情況下,CI930F的控制邏輯會切換到線路B,同樣的道理,如果B線路出錯,會自動切換到A。
Features 功能 |
|
Protocol 協議 |
PROFIBUS-DP master V0/V1 PROFIBUS-DP主 |
Fieldbus connection 現場匯流排連線 |
D-SUB, 9-pin, female connector 9針母頭 |
Internal power supply 內部供電 |
Via coupler bus 通過耦合器匯流排 |
LEDs LED燈 |
Five LEDs for status display |
Use 用於 |
AC 900F |
Form factor 外形 |
AC 900F |
Number of slaves 可掛從站數量 |
125 |
Controller redundancy support 支援冗餘控制器 |
YES |
Hot plug 熱插拔 |
YES |
HCIR | YES |
Line redundancy 線路冗餘 |
YES |
LED status displays
LED燈狀態顯示
After having been switched on, the CI 930 PROFIBUS module performs a self-testduring power-up. During initialization, with newly configured modules or after achange of the operating mode, all LEDs may light up briefly before reaching thedefined status.
上電後,CI 930 PROFIBUS模板執行自檢。在初始化過程中,使用新配置的模組或在操作模式更改後,所有 LED 可能會在達到定義狀態之前短暫亮起。
Line redundancy OFF
LED A (line A)
LED 燈 |
Color 顏色 |
Status 狀態 |
Meaning 含義 |
PWR 電源燈 |
GREEN 綠色 |
ON 亮 |
Module in operation and must not be removed 模板正在使用,不能被拆除 |
OFF 滅 |
Module not in operation and may be removed, if required 模板沒有使用,如果需要,可以拆除 |
||
STA 狀態燈 |
Green 綠色 |
ON 亮 |
Active module operating properly 活動模組,正常執行 |
OFF 滅 |
Module start-up 模組啟動 |
||
Orange 橙色 |
ON 亮 |
Module identified by the CPU module, but inactive CPU識別出模組,但模組沒有執行 |
|
Red 紅色 |
ON 亮 |
Module error 模板錯誤 |
|
RUN 執行燈 |
GREEN 綠色 |
ON 亮 |
Module has taken over the master function 模組接管“主”功能 |
OFF 滅 |
Module inactive relative to the PROFIBUS 模板的PROFIBUS非活動狀態 |
||
GREEN 綠色 |
200ms plus |
Module ready to take over the master function 模板計劃接管“主”功能 |
|
Line redundancy OFF 線路冗餘滅 | |||
LED A (Line A) |
GREEN |
ON 亮 |
Bus traffic 有匯流排通訊 |
OFF 滅 |
No bus traffic 無匯流排通訊 |
Line redundancy ON 冗餘線路燈亮 |
||||
LED A(Line A) | LED B(Line B) |
LED A and B must be considered as a pair LED A和LED B必須視為成對 |
||
Color 顏色 |
Status 狀態 |
Color 顏色 |
Status 狀態 |
|
GREEN 綠色 |
ON 亮 |
GREEN 綠色 |
ON 亮 |
Data reception on both lines, A and B A和B兩路資料接收 |
OFF 滅 |
OFF 滅 |
No data reception on lines A and B A和B沒有資料接收 |
||
RED 紅色 |
ON 亮 |
GREEN 綠色 |
ON 亮 |
No data reception on line A, but data reception on line B 線路A沒有資料接收,線路B有資料接收 |
GREEN | ON | RED | ON |